7 Operation
Maschinenfabrik Reinhausen GmbH 2019
115
5163667/06 EN
ETOS
®
IM
If the measured voltage U
actual
deviates from the set bandwidth for a long
period
, a control impulse is output to the motor-drive unit after the set de-
lay time T1
. If the measured voltage U
actual
is still outside the bandwidth,
delay time T2
starts once delay time T1 is complete. Once delay time T2
is complete, a control impulse is again output to the motor-drive unit for the
tap change
to return to the tolerance bandwidth.
Figure 94: Behavior of the regulation function with delay times T1 and T2
1 + B %: Upper limit
4 Set delay times T1 and T2.
2 U
desired
: Desired value
5 U
actual
: Measured voltage
3 - B %: Lower limit
6 B%: Tolerance bandwidth
A U
actual
is outside the bandwidth. De-
lay time T1 starts.
B Delay time T1 complete. Tap
change triggered.
C Delay time T2 complete. Tap
change triggered.
Setting delay time T2
To set the delay time T2 proceed as follows:
1. Go to
Settings > Parameters > Control > Delay time T2
.
2. Set delay time T2.
3. Press the
Accept
button to save the modified parameter.
Activating delay time T2
To activate delay time T2, proceed as follows:
1. Go to
Settings > Parameters > Control > Activate delay T2
.