7 Operation
Maschinenfabrik Reinhausen GmbH 2019
288
5163667/06 EN
ETOS
®
IM
Figure 210: Configuring Modbus data points
Proceed as follows to configure the data points:
1. Go to
Settings > Data point configuration
.
2. Adjust the data points as required.
3. Press the
Accept
button to adopt the modified list of data points.
4. Restart the device to activate the modified list of data points.
7.23.8.5 Configuring DNP3 data points
You can adjust the following data point properties for the DNP3 control sys-
tem protocol:
Column
Description
Modifiable
Setting range
Active
You can use the checkbox to set whether the data point is
to be transferred via the control system protocol or not.
Yes
Active/inactive
OBJGROUP
The OBJGROUP column indicates the data point object
group:
▪ AI = Analog Input
▪ AO = Analog Output
▪ BI = Binary Input
▪ BO = Binary Output
▪ CT = Counter
No
-
INDEXADDR
Data point address.
Yes
0...4,294,967,296
CLASS
Data point class.
▪ 0: Static
▪ 1...3: Event
Notice: You can only set the data point class for data
points of object groups AI, BI, and CT.
Yes
0...3