7 Operation
Maschinenfabrik Reinhausen GmbH 2019
284
5163667/06 EN
ETOS
®
IM
Column
Description
Modifiable
Setting range
TH
Threshold value for measured values. The data point is
only transferred again if the change of value is greater
than the threshold value.
▪ If you enter the value 0, no threshold value is active.
▪ If you do not enter any value, the device adopts the
threshold value defined by the device parameter. If no
device parameter is available for the threshold value,
no threshold value is active either.
▪ Notice: You can only enter a threshold value for data
points of type 9, 10, 11, 12, 13, 14, 21, 34, 35 or 36.
Yes
0...32,768
CT
Interval in ms for periodic transmission of the data point. If
you set 0, the data point is not transmitted periodically.
Notice: You can only enter an interval for data points of
type 9, 11 or 13.
Yes
0...10,000
Table 78: Configuring IEC 60870-5-101 data points
Figure 207: Configuring IEC 60870-5-101 data points
Proceed as follows to configure the data points:
1. Go to
Settings > Data point configuration
.
2. Adjust the data points as required.
3. Press the
Accept
button to adopt the modified list of data points.
4. Restart the device to activate the modified list of data points.