![MR ETOS IM Скачать руководство пользователя страница 23](http://html.mh-extra.com/html/mr/etos-im/etos-im_operating-instructions-manual_1844393023.webp)
3 IT security
Maschinenfabrik Reinhausen GmbH 2019
23
5163667/06 EN
ETOS
®
IM
Interface
Protocol
Port
Description
CAN 1
-
-
Attachment of the DIO assembly
CAN 2
-
-
Communication with other ISM® devices
(e.g. parallel operation)
COM 1
-
-
Internal system interface
COM 2
-
-
Serial interface (SCADA)
USB
-
-
Import or export of data
ETH 1
TCP
102
IEC 61850
2)
ETH 1
TCP
502
Modbus
2)
ETH 1
TCP
20000
DNP3
2)
ETH 1
UDP
67
DHCP server
ETH 2.x
TCP
21
FTP
1)
(only for MR service)
ETH 2.x
TCP
80
HTTP for web-based visualization
1)
ETH 2.x
TCP
443
HTTPS for web-based visualization
1)
ETH 2.x
TCP
990
FTPS (only for MR service)
ETH2.x
TCP
8080
HTTP for web-based visualization
1)
ETH2.x
TCP
8081
HTTPS for web-based visualization
1)
Table 5: Interfaces and open ports of the CPU assembly
1)
Port is closed if you activate the device's SSL encryption.
2)
Default setting; if you have modified the port for the control system proto-
col, only the set port is opened.
Encryption standards
The device supports the following TLS versions:
▪ TLS 1.0
▪ TLS 1.1
▪ TLS 1.2
The device uses the following cipher suites for a TLS-secured connection:
Key exchange
Authentication
Encryption
Key length
Operating
mode
Hash func-
tion
TLS
ECDHE
RSA
WITH
AES
128
CBC
SHA
1)
DHE
SHA265
ECDHE
ECDSA
GCM
SHA256
ECDH
256
CBC
SHA
1)
RSA
1)
SHA256
GCM
SHA384
Table 6: Cipher suite