9 Messages
Maschinenfabrik Reinhausen GmbH 2019
362
5163667/06 EN
ETOS
®
IM
No.
Name
Description
Remedy
Q
1
1225
F1-tanδ: Dissipation factor
monitoring deactivated
Dissipation factor monitoring has
been deactivated in field 1.
Activate dissipation factor moni-
toring of the bushings for field 1.
-
1226
F1-tanδ: Measured voltage
too low
Dissipation factor monitoring not
performed in field 1 due to the
voltage on the bushing coupling
units being too low.
Check the bushing coupling units,
the wiring, the bushings and the
transformer operating conditions
in field 1.
-
1234
Power factor active
The power factor parallel opera-
tion mode is carried out as CAN
bus communication is not possi-
ble with other devices.
CAN bus communication is not
possible with other devices.
Check wiring as per connection
diagram.
-
1235
Motor Current Index TSO/
CSO>
The limit value for the connection
type tap selector operation /
change-over selector operation
has been exceeded.
Check the motor-drive unit.
-
1236
Motor Current Index TSO/
CSO <
The value for the connection type
tap selector operation / change-
over selector operation has fallen
below the limit value.
Check the motor-drive unit.
-
1237
Motor Current Index RSO >
The limit value for the connection
type reverse tap-change opera-
tion has been exceeded.
Check the motor-drive unit.
-
1238
Motor Current Index RSO <
The value for the connection type
reverse tap-change operation has
fallen bellow the limit value.
Check the motor-drive unit.
-
1239
Relative paper moisture in-
valid
The relative paper moisture can-
not be calculated.
Check the sensors, the wiring of
the device, and the configuration
of the analog signals for recording
H2O content in the oil and for the
hot-spot calculation.
-
1240
Analog output for bottom-oil
temp.
The value cannot be output via
the analog output.
Check the configuration of the
analog input for recording bottom-
oil temperature, the set parame-
ters, and the wiring of the analog
output.
-
1241
Analog output for relative
moisture in oil
The value cannot be output via
the analog output.
Check the configuration of the
analog input for recording relative
moisture in oil, the set parame-
ters, and the wiring of the analog
output.
-
1242
Analog output for H2
The value cannot be output via
the analog output.
Check the configuration of the
analog input for recording hydro-
gen content, the set parameters,
and the wiring of the analog out-
put.
-
1243
Analog output for N2
The value cannot be output via
the analog output.
Check the configuration of the
analog input for recording nitro-
gen content, the set parameters,
and the wiring of the analog out-
put.
-