![MR ETOS IM Скачать руководство пользователя страница 101](http://html.mh-extra.com/html/mr/etos-im/etos-im_operating-instructions-manual_1844393101.webp)
7 Operation
Maschinenfabrik Reinhausen GmbH 2019
101
5163667/06 EN
ETOS
®
IM
Setting desired value 1
To set the desired value, proceed as follows:
1. Go to
Settings > Parameters > Control > Desired value
.
2. Enter desired value.
3. Press the
Accept
button to save the modified parameter.
Setting desired value step width
To set the desired value sep width, proceed as follows:
1. Go to
Settings > Parameters > Control > Desired value step width
.
2. Enter desired value step width.
3. Press the
Accept
button to save the modified parameter.
Also refer to
2
7.3.1.6 Active power-dependent adjustment of desired voltage value
The TAPCON® Dynamic Setpoint Control (TDSC) function is used to adapt
the desired voltage value depending on the measured active power. This al-
lows you to compensate for a voltage drop during increased load or an in-
crease in voltage due to a decentralized feed-in.
Depending on whether positive or negative active power is measured, the
desired value calculation is based on 2 linear equations (see example in dia-
gram below).
Parameter
Function
Settings (see diagram
below)
U
max
: Maximum desired value
Maximum set desired value is activated when P
max
is
exceeded.
103.0 V
U
min
: Minimum desired value
Minimum set desired value is activated when value falls
below P
min
.
99.0 V
U
0
: Desired value at 0 active
power
Set desired value is activated when measured active
power is 0 MW.
100.00 V
P
max
: Active power at max. de-
sired value
Set maximum active power value above which the
power-dependent desired value is to attain the maxi-
mum value U
max
.
20.0 MW
P
min
: Active power at min. desired
value
Set minimum active power value below which the
power-dependent desired value is to attain the mini-
mum value U
min
.
-20.0 MW
Table 16: Parameters to be set for active power-dependent adjustment of desired voltage value