9 Messages
Maschinenfabrik Reinhausen GmbH 2019
356
5163667/06 EN
ETOS
®
IM
No.
Name
Description
Remedy
Q
1
1112
Top-oil temperature > limit
value
Top-oil temperature is greater
than > limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1113
Top-oil temperature >> limit
value
Top-oil temperature is greater
than >> limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1114
Top-oil temperature < limit
value
Top-oil temperature is less than
the < limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1115
Top-oil temperature << limit
value
Top-oil temperature is less than
the << limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1116
N2 invalid
The analog signal for recording
the proportion of nitrogen in the
oil is invalid.
Check the sensor, device wiring
and analog signal configuration.
-
1117
O2 invalid
The analog signal for recording
the proportion of oxygen in the oil
is invalid.
Check the sensor, device wiring
and analog signal configuration.
-
1118
OLTC oil level invalid
The analog signal for recording
the on-load tap-changer's oil level
is invalid.
Check the sensor, device wiring
and analog signal configuration.
-
1119
Transformer oil level invalid
The analog signal for recording
the transformer's oil level is in-
valid.
Check the sensor, device wiring
and analog signal configuration.
-
1120
Transformer oil pressure in-
valid
The analog signal for recording
the transformer's oil pressure is
invalid.
Check the sensor, device wiring
and analog signal configuration.
-
1121
OLTC oil temperature invalid
The analog signal for recording
the on-load tap-changer's oil tem-
perature is invalid.
Check the sensor, device wiring
and analog signal configuration.
-
1122
TDCG invalid
The analog signal for recording
the combustible gases is invalid.
Check the sensor, device wiring
and analog signal configuration.
-
1123
Upper oil temperature invalid
The analog signal for recording
the upper oil temperature is in-
valid.
Check the sensor, device wiring
and analog signal configuration.
-
1124
Cooling system control error
Load current signal or tempera-
ture input signal invalid.
Check the temperature and cur-
rent transformer inputs.
-
1125
Periodic mode active
Cooling stages are switched on
by the periodic mode.
Periodic switching on has taken
place.
-
1126
Load-dep. mode active
The load threshold of the cooling
system control's load-dependent
mode has been exceeded. All
cooling stages active.
Check the current operating con-
ditions of the transformer and the
set parameters for the load-de-
pendent mode.
-