9 Messages
Maschinenfabrik Reinhausen GmbH 2019
361
5163667/06 EN
ETOS
®
IM
No.
Name
Description
Remedy
Q
1
1210
F1-C: Standardization mea-
sured voltage too high
Standardization of field 1 not per-
formed due to the voltage on the
bushing coupling units being too
high.
Check the bushing coupling units,
the wiring, the bushings and the
transformer operating conditions
in field 1.
A
1211
F1-C: Standardization wiring
error
Standardization of field 1 not per-
formed due to a wiring error.
Check the wiring of the bushing
coupling units and the reference
system in field 1.
A
1212
F1-C: Standardization voltage
deviation too high
Standardization of field 1 not per-
formed due to the voltage devia-
tion in the 3 phases of the refer-
ence system being too high.
Check the reference system and
the wiring in field 1.
A
1213
F1-C: Standardization config-
uration implausible
Standardization of field 1 not per-
formed due to an implausible con-
figuration.
Check the set parameters, the
reference system, the bushing
coupling units, the wiring, the
bushings and the transformer op-
erating conditions in field 1.
A
1214
F1-C: Standardization mea-
surement system unstable
Standardization of field 1 not per-
formed due to an unstable mea-
surement system.
Check the reference system, the
bushing coupling units, the wiring,
and the transformer operating
conditions in field 1.
A
1215
F1-C: Standardization not per-
formed
Capacitance monitoring not per-
formed in field 1 due to standard-
ization not being performed.
Perform standardization of the ca-
pacitance monitoring for field 1.
-
1216
F1-tanδ: Limit value Δtanδ >
phase L1
The limit value for the deviation of
the dissipation factor has been
exceeded for the bushing of
phase L1 in field 1.
Check the curve for the change in
dissipation factor in field 1. Check
the dissipation factor of the bush-
ing using an external measuring
device.
-
1217
F1-tanδ: Limit value Δtanδ >
phase L2
The limit value for the deviation of
the dissipation factor has been
exceeded for the bushing of
phase L2 in field 1.
Check the curve for the change in
dissipation factor in field 1. Check
the dissipation factor of the bush-
ing using an external measuring
device.
-
1218
F1-tanδ: Limit value Δtanδ >
phase L3
The limit value for the deviation of
the dissipation factor has been
exceeded for the bushing of
phase L3 in field 1.
Check the curve for the change in
dissipation factor in field 1. Check
the dissipation factor of the bush-
ing using an external measuring
device.
-
1219
F1-tanδ: Limit value Δtanδ >
multiple phases
The limit value for the deviation of
the dissipation factor has been
exceeded for the bushings of mul-
tiple phases in field 1.
Check the reference system and
the curves for the changes in dis-
sipation factor in field 1. Check
the dissipation factor of the bush-
ings using an external measuring
device.
-
1224
F1-tanδ: Phase angle devia-
tion too high
Dissipation factor monitoring not
performed in field 1 due to the
phase angle deviation of the 3
phases of the reference system
being too high.
Check the reference system and
the wiring in field 1.
-