No.
Name
Description
Remedy
Q
1
1014
Generic temperature 5 invalid
The analog signal for recording
the generic temperature 5 is in-
valid.
Check the sensor, device wiring
and analog signal configuration.
-
1015
Generic temperature 6 invalid
The analog signal for recording
the generic temperature 6 is in-
valid.
Check the sensor, device wiring
and analog signal configuration.
-
1016
Generic temperature 7 invalid
The analog signal for recording
the generic temperature 7 is in-
valid.
Check the sensor, device wiring
and analog signal configuration.
-
1017
Generic temperature 8 invalid
The analog signal for recording
the generic temperature 8 is in-
valid.
Check the sensor, device wiring
and analog signal configuration.
-
1018
H2 invalid
The analog signal for recording
the proportion of hydrogen in the
oil is invalid.
Check the sensor, device wiring
and analog signal configuration.
-
1019
Hot-spot temperature invalid
The analog signal for recording
the hot-spot temperature is invalid
or invalid parameters were set for
the hot-spot calculation.
Check the sensor, device wiring,
and analog signal configuration
and the parameters for the hot-
spot calculation.
-
1020
Hot-spot temperature winding
1 invalid
Invalid analog signal for recording
the hot-spot temperature of wind-
ing 1 or invalid parameters for the
hot-spot calculation.
Check the sensor, device wiring,
and analog signal configuration
and the parameters for the hot-
spot calculation.
-
1021
Hot-spot temperature winding
2 invalid
Invalid analog signal for recording
the hot-spot temperature of wind-
ing 2 or invalid parameters for the
hot-spot calculation.
Check the sensor, device wiring,
and analog signal configuration
and the parameters for the hot-
spot calculation.
-
1022
Hot-spot temperature winding
3 invalid
Invalid analog signal for recording
the hot-spot temperature of wind-
ing 3 or invalid parameters for the
hot-spot calculation.
Check the sensor, device wiring,
and analog signal configuration
and the parameters for the hot-
spot calculation.
-
1023
Relative moisture in oil invalid
The analog signal for recording
the proportion of H2O in the oil is
invalid.
Check the sensor, device wiring
and analog signal configuration.
-
1024
Relative loss-of-life > limit
value
Relative loss-of-life is greater than
> limit value.
Check the current operating con-
ditions of the transformer, the pa-
rameters for calculating the rela-
tive loss-of-life, and the set limit
value.
-
1025
Relative loss-of-life >> limit
value
Relative loss-of-life is greater than
>> limit value.
Check the current operating con-
ditions of the transformer, the pa-
rameters for calculating the rela-
tive loss-of-life, and the set limit
value.
-
1026
Ambient temperature > limit
value
Ambient temperature is greater
than > limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-