7 Operation
Maschinenfabrik Reinhausen GmbH 2019
276
5163667/06 EN
ETOS
®
IM
To set the number of repetitions for unsolicited messages, proceed as fol-
lows:
1. Go to
Settings > Parameters > DNP3 > Repetition of unsolicited mes-
sages
.
2. Enter the desired number.
3. Press the
Accept
button to save the modified parameter.
Repeat unsolicited messages indefinitely
You can use this parameter to set the device to send an indefinite number of
unsolicited messages until it receives a response from the DNP3 master.
To set an indefinite number of unsolicited message repetitions, proceed as
follows:
1. Go to
Settings > Parameters > DNP3 > Repeat unsolicited messages
indefinitely
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
Timeout confirmation
You can use this parameter to set the timeout for unsolicited messages.
To set the timeout for unsolicited messages, proceed as follows:
1. Go to
Settings > Parameters > DNP3 > Timeout
.
2. Enter the timeout.
3. Press the
Accept
button to save the modified parameter.
Timeout for response confirmation
You can use this parameter to set the timeout for response confirmation for
unsolicited messages.
To set the timeout for response confirmation, proceed as follows:
1. Go to
Settings > Parameters > DNP3 > Timeout for response confir-
mation
.
2. Enter the timeout.
3. Press the
Accept
button to save the modified parameter.
User ID code
You can use this parameter to set the user ID code.
To set the user ID code, proceed as follows:
1. Go to
Settings > Parameters > DNP3 > User ID code
.
2. Enter the user ID code.
3. Press the
Accept
button to save the modified parameter.