9 Messages
Maschinenfabrik Reinhausen GmbH 2019
365
5163667/06 EN
ETOS
®
IM
No.
Name
Description
Remedy
Q
1
1264
Analog output for ambient
temp.
The value cannot be output via
the analog output.
Check the configuration of the
analog input for recording ambi-
ent temperature, the set parame-
ters, and the wiring of the analog
output.
-
1265
Analog output for hot-spot
temp.
The value cannot be output via
the analog output.
Check the configuration of the
analog input for recording the hot-
spot temperature, the set param-
eters, and the wiring of the analog
output.
-
1266
Analog output for hot-spot
temp. winding 1
The value cannot be output via
the analog output.
Check the configuration of the
analog input for recording the hot-
spot temperature in the first wind-
ing, the set parameters, and the
wiring of the analog output.
-
1267
Analog output for hot-spot
temp. winding 2
The value cannot be output via
the analog output.
Check the configuration of the
analog input for recording the hot-
spot temperature in the second
winding, the set parameters, and
the wiring of the analog output.
-
1268
Analog output for hot-spot
temp. winding 3
The value cannot be output via
the analog output.
Check the configuration of the
analog input for recording the hot-
spot temperature in the third
winding, the set parameters, and
the wiring of the analog output.
-
1269
Analog output for bubble tem-
perature
The value cannot be output via
the analog output.
Check the sensors, the wiring of
the device, and the configuration
for recording paper moisture.
-
1270
Analog output for loss-of-life
The value cannot be output via
the analog output.
Check the parameter settings and
the wiring of the analog output.
-
1271
Analog output for paper mois-
ture
The value cannot be output via
the analog output.
Check the sensors, the wiring of
the device, and the configuration
of the analog signals for recording
H2O content in the oil and for the
hot-spot calculation.
-
1272
F1-tanδ: Standardization not
performed
Dissipation factor monitoring not
performed in field 1 due to stan-
dardization not being performed.
Perform standardization of the
dissipation factor monitoring for
field 1.
-
1273
F1-C: Capacitance monitoring
inactive
Capacitance monitoring is not
currently being performed for field
1.
Capacitance monitoring will be
performed for field 1 after a delay
time has elapsed.
-
1274
F1-tanδ: Dissipation factor
monitoring inactive
Dissipation factor monitoring is
not currently being performed for
field 1.
Dissipation factor monitoring will
be performed for field 1 after a
delay time has elapsed.
-
1275
Impermissible supply voltage
The supply voltage is in an imper-
missible range.
Check your supply voltage.
-
1276
Even tap position
The on-load tap-changer is in an
even tap position.
This event will be reset automati-
cally as soon as the tap changer
is in an odd tap position.
-