7 Operation
Maschinenfabrik Reinhausen GmbH 2019
127
5163667/06 EN
ETOS
®
IM
Parameter
Option
Phase angle correction
0°
UI measuring channels
3-ph. voltage, 1-ph. current
Measurement mode
Phase-neutral
Table 33: Circuit 3-F
Circuit 3-G
▪ Three-phase voltage measurement, single-phase current measurement.
▪ The voltage transformers are connected between the phase and neutral
conductor.
▪ The current transformer is connected to phase L2.
Parameter
Option
Voltage-transformer circuit
3 Ph phase voltage
Current-transformer circuit
3 Ph phase current
Phase angle correction
-120°
UI measuring channels
3-ph. voltage, 1-ph. current
Measurement mode
Phase-neutral
Table 34: Circuit 3-G
Circuit 3-H