Test parameters
Max. test voltage
Max. test dura-
tion
Ramp
Breaking current
threshold
DIO 28-15
DIO 42-20
DIO 42-20 HL
any DI, DO
2.2 kV AC
2 s
5 s
> 1 mA
G1 (PULS)
N, L
2.2 kV AC
2 s
5 s
> 4 mA
Table 13: Permitted interfaces and test parameters for the dielectric test
1)
only the version with 85...265 VAC/VDC wide-range power supply, other-
wise the device may be damaged. Note the nameplate.
Sample dielectric test set-up
Figure 80: Sample set-up of the dielectric test for a device designed with the OT 1205 wide-range power supply