12 Technical data
Maschinenfabrik Reinhausen GmbH 2019
389
5163667/06 EN
ETOS
®
IM
DIO 28-15
DIO 42-20
DIO 42-20 HL
Outputs (floating re-
lay outputs)
Number (number of
change-over contacts in
parentheses)
15 (9)
20 (12)
Contact loadability
Max. AC: 230 V AC; 5 A
Max. DC: See diagram
Simultaneity factor
up to 60 °C: 100%, > 60 °C: -5%/K
Table 132: Technical data for the DIO 28-15 and DIO 42-20 assemblies
10
20
30
40
50
100
V
300
0.1
0.2
0.5
1
2
5
10
20
A
U
I
Figure 261: Contact loadability of digital outputs with resistive load
CAUTION
Electric shock!
The inputs of the DIO assembly have plug-based electrical isolation. A mix-
ture of voltage ranges (e.g. extra low voltage and low voltage) or various
phases within a plug can lower the protection against electric shock.
► Use the same voltage ranges within a plug.