7 Operation
Maschinenfabrik Reinhausen GmbH 2019
157
5163667/06 EN
ETOS
®
IM
Setting
Behavior
Auto blocking
▪ The
Reversal of power flow
event is issued.
▪ If Z compensation is activated, this function is deacti-
vated.
▪ Automatic regulation is blocked.
Auto/manual blocking
▪ The
Reversal of power flow
event is issued.
▪ If Z compensation is activated, this function is deacti-
vated.
▪ Automatic regulation is blocked.
▪ You cannot perform tap-change operations in manual
mode.
Target tap position
▪ The
Reversal of power flow
event is issued.
▪ If Z compensation is activated, this function is deacti-
vated.
▪ The device triggers a tap-change operation to the tap
position you defined in the "Target tap posi-
tion" [
Section 7.9, Page 168] parameter.
▪ The device blocks further tap-change operations.
▪ The target-tap-position operation is ignored if there is
no tap-position capture. Automatic regulation is
blocked.
Table 49: Behavior in the event of a reversal of power flow
7.8.5 Tap position monitoring (optional)
You can set 2 limit values for tap position monitoring:
▪ Pos<
▪ Pos>
You can set the following parameters for each limit value.
▪ Delay time (optional)
▪ Behavior limit value
Delay time limit value
You can use this parameter to set the delay time in order to delay the issuing
of the event message.