ETOS
®
IM
No.
Name
Description
Remedy
Q
1
1298
F2-C: Limit value ΔC1 >>
phase L3
The second limit value for the de-
viation in capacitance has been
exceeded for the bushing of
phase L3 in field 2.
Check capacitance changes in
field 2. If ∆C1 is greater than
10%, there is a risk of explosion.
Disconnect transformer from the
grid immediately. Use an external
measuring device to measure ca-
pacitance.
A
1299
F2-C: Limit value ΔC1 >> mul-
tiple phases
The second limit value for the de-
viation in capacitance has been
exceeded for the bushings of mul-
tiple phases in field 2.
Check reference system and ca-
pacitance changes in field 2. If
∆C1 is greater than 10%, there is
a risk of explosion. Disconnect
transformer from the grid immedi-
ately. Use an external measuring
device to measure capacitance.
A
1300
F2-C: Standardization inactive You cannot currently perform
standardization of the capaci-
tance monitoring for field 2.
You can perform standardization
of the capacitance monitoring for
field 2 after a delay time has
elapsed.
-
1301
F2-C: Standardization refer-
ence voltage invalid
Standardization of field 2 not per-
formed due to an invalid refer-
ence voltage measurement.
Check the reference system and
the wiring in field 2.
A
1302
F2-C: Standardization refer-
ence voltage too low
Standardization of field 2 not per-
formed due to the reference volt-
age being too low.
Check the reference system and
the wiring in field 2.
A
1303
F2-C: Standardization mea-
sured voltage invalid
Standardization of field 2 not per-
formed due to an invalid voltage
measurement on the bushing
coupling units.
Check the bushing coupling units,
the wiring, the bushings and the
transformer operating conditions
in field 2.
A
1304
F2-C: Standardization mea-
sured voltage too low
Standardization of field 2 not per-
formed due to the voltage on the
bushing coupling units being too
low.
Check the bushing coupling units,
the wiring, the bushings and the
transformer operating conditions
in field 2.
A
1305
F2-C: Standardization mea-
sured voltage too high
Standardization of field 2 not per-
formed due to the voltage on the
bushing coupling units being too
high.
Check the bushing coupling units,
the wiring, the bushings and the
transformer operating conditions
in field 2.
A
1306
F2-C: Standardization wiring
error
Standardization of field 2 not per-
formed due to a wiring error.
Check the wiring of the bushing
coupling units and the reference
system in field 2.
A
1307
F2-C: Standardization voltage
deviation too high
Standardization of field 2 not per-
formed due to the voltage devia-
tion in the 3 phases of the refer-
ence system being too high.
Check the reference system and
the wiring in field 2.
A
1308
F2-C: Standardization config-
uration implausible
Standardization of field 2 not per-
formed due to an implausible con-
figuration.
Check the set parameters, the
reference system, the bushing
coupling units, the wiring, the
bushings and the transformer op-
erating conditions in field 2.
A