9 Messages
Maschinenfabrik Reinhausen GmbH 2019
354
5163667/06 EN
ETOS
®
IM
No.
Name
Description
Remedy
Q
1
1087
Hot-spot >> limit value
Hot-spot temperature is greater
than >> limit value.
Check the current operating con-
ditions of the transformer, the pa-
rameters for calculating the hot-
spot temperature, and the set
limit value.
-
1088
Loss-of-life > limit value
Loss-of-life is greater than > limit
value.
Check the current operating con-
ditions of the transformer, the pa-
rameters for calculating the loss-
of-life, and the set limit value.
-
1089
Loss-of-life >> limit value
Loss-of-life is greater than >> limit
value.
Check the current operating con-
ditions of the transformer, the pa-
rameters for calculating the loss-
of-life, and the set limit value.
-
1090
N2 > limit value
N2 proportion is greater than >
limit value.
Check the current operating con-
ditions of the transformer, sensor,
analog signal configuration and
the set limit value.
-
1091
N2 >> limit value
N2 proportion is greater than >>
limit value.
Check the current operating con-
ditions of the transformer, sensor,
analog signal configuration and
the set limit value.
-
1092
O2 > limit value
O2 proportion is greater than >
limit value.
Check the current operating con-
ditions of the transformer, sensor,
analog signal configuration and
the set limit value.
-
1093
O2 >> limit value
O2 proportion is greater than >>
limit value.
Check the current operating con-
ditions of the transformer, sensor,
analog signal configuration and
the set limit value.
-
1094
OLTC oil level > limit value
Oil level of on-load tap-changer is
greater than > limit value.
Check the on-load tap-changer oil
level and the device wiring. If us-
ing an analog sensor, check the
sensor, analog signal configura-
tion, and the set limit value.
-
1095
OLTC oil level >> limit value
Oil level of on-load tap-changer is
greater than >> limit value.
Check the on-load tap-changer oil
level and the device wiring. If us-
ing an analog sensor, check the
sensor, analog signal configura-
tion, and the set limit value.
-
1096
OLTC oil level < limit value
Oil level of on-load tap-changer is
less than < limit value.
Check the on-load tap-changer oil
level and the device wiring. If us-
ing an analog sensor, check the
sensor, analog signal configura-
tion, and the set limit value.
-
1097
OLTC oil level << limit value
Oil level of on-load tap-changer is
less than << limit value.
Check the on-load tap-changer oil
level and the device wiring. If us-
ing an analog sensor, check the
sensor, analog signal configura-
tion, and the set limit value.
-