No.
Name
Description
Remedy
Q
1
1178
Door open
The control cabinet door is open.
Close the control cabinet door.
-
1179
F1: Bushing monitoring refer-
ence voltage invalid
Bushing monitoring not performed
in field 1 due to an invalid refer-
ence voltage measurement.
Check the reference system and
the wiring in field 1.
-
1180
F1: Bushing monitoring mea-
sured voltage invalid
Bushing monitoring not performed
in field 1 due to an invalid voltage
measurement on the bushing
coupling units.
Check the bushing coupling units,
the wiring, the bushings and the
transformer operating conditions
in field 1.
-
1181
F1-C: Implausible configura-
tion
Capacitance monitoring not per-
formed in field 1 due to an im-
plausible parameter configuration.
Check the parameters set for field
1.
-
1182
F1-C: Voltage deviation too
high
Capacitance monitoring not per-
formed in field 1 due to the volt-
age deviation in the 3 phases of
the reference system being too
high.
Check the reference system and
the wiring in field 1.
-
1183
F1-C: Capacitance monitoring
deactivated
Capacitance monitoring has been
deactivated for field 1.
Activate capacitance monitoring
of the bushings for field 1.
-
1184
F1-C: Limit value ΔC1 >
phase L1
The first limit value for the devia-
tion in capacitance has been ex-
ceeded for the bushing of phase
L1 in field 1.
Check field 1 capacitance
changes. If ∆C1 is greater than
5%, disconnect the transformer
from the grid. Use an external
measuring device to measure ca-
pacitance.
A
1185
F1-C: Limit value ΔC1 >
phase L2
The first limit value for the devia-
tion in capacitance has been ex-
ceeded for the bushing of phase
L2 in field 1.
Check field 1 capacitance
changes. If ∆C1 is greater than
5%, disconnect the transformer
from the grid. Use an external
measuring device to measure ca-
pacitance.
A
1186
F1-C: Limit value ΔC1 >
phase L3
The first limit value for the devia-
tion in capacitance has been ex-
ceeded for the bushing of phase
L3 in field 1.
Check field 1 capacitance
changes. If ∆C1 is greater than
5%, disconnect the transformer
from the grid. Use an external
measuring device to measure ca-
pacitance.
A
1190
F1-C: Limit value ΔC1 > multi-
ple phases
The first limit value for the devia-
tion in capacitance has been ex-
ceeded for the bushings of multi-
ple phases in field 1.
Check reference system and field
1 capacitance changes. If ∆C1 is
greater than 5%, disconnect the
transformer from the grid. Use an
external measuring device to
measure capacitance.
A
1191
F1-C: Limit value ΔC1 >>
phase L1
The second limit value for the de-
viation in capacitance has been
exceeded for the bushing of
phase L1 in field 1.
Check field 1 capacitance
changes. If ∆C1 is greater than
10%, there is a risk of explosion.
Disconnect transformer from the
grid immediately. Use an external
measuring device to measure ca-
pacitance.
A