7 Operation
Maschinenfabrik Reinhausen GmbH 2019
269
5163667/06 EN
ETOS
®
IM
Option
Description
Ed. 1 Amendment2
Optimization in accordance with IEC 60870 Edition 1,
Amendment 2 (Type 1, 3, 9, 11, 13, 15 21, 126).
Ed. 2
Optimization in accordance with IEC 60870 Edition 2
(Type 1, 3, 5, 7, 9, 11, 13, 15, 20, 21, 126).
Table 74: ASDU sequence optimization
To set the ASDU sequence optimization, proceed as follows:
1. Go to
Settings > Parameters > IEC 60870-5-104 > ASDU sequence op-
timization
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
Reference time
You can use this parameter to set which time is to be transmitted by the con-
trol system. The device uses this information for time synchronization
[
Section 7.25, Page 292]. You can select the following options:
Option
Description
Local
The control system transmits the local time.
Section 7.25.5, Page 295]. Otherwise
the device will use an incorrect time.
UTC
The control system transmits the time as UTC. The de-
vice calculates the local time from UTC and the set time
zone [
Table 75: Reference time
To set the reference time, proceed as follows:
1. Go to
Settings > Parameters > IEC 60870-5-104 > Reference time
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
Содержание ETOS IM
Страница 1: ...Monitoring system ETOS IM Operating instructions 5163667 06 EN ...
Страница 410: ......
Страница 411: ......