![MR ETOS IM Скачать руководство пользователя страница 268](http://html.mh-extra.com/html/mr/etos-im/etos-im_operating-instructions-manual_1844393268.webp)
7 Operation
Maschinenfabrik Reinhausen GmbH 2019
268
5163667/06 EN
ETOS
®
IM
Gateway address
You can use this parameter to set the gateway's IP address.
If you set the value to 0.0.0.0, no gateway is used.
To set the gateway address, proceed as follows:
1. Go to
Settings > Parameters > IEC 60870-5-104 > Gateway address
.
2. Enter the gateway address.
3. Press the
Accept
button to save the modified parameter.
TCP port
You can use this parameter to set the TCP port.
To set the TCP port, proceed as follows:
1. Go to
Settings > Parameters > IEC 60870-5-104 > TCP port
.
2. Enter the TCP port.
3. Press the
Accept
button to save the modified parameter.
ASDU address
You can use this parameter to set the address of the ASDU.
To set the ASDU address, proceed as follows:
1. Go to
Settings > Parameters > IEC 60870-5-104 > ASDU address
.
2. Set ASDU address.
3. Press the
Accept
button to save the modified parameter.
ASDU sequence optimization
With this parameter, you can set which method is to be used for optimizing
the ASDU types. The standard enables optimization in order to be able to
transfer multiple value changes in a telegram in a sequence of ascending in-
formation object addresses. This is displayed by the sequence bit. The se-
lection of ASDU types for which this optimization is allowed is based on the
edition of the standard.
You can select the following options:
Option
Description
None
The device does not optimize the ASDU types.
Ed. 1
Optimization in accordance with IEC 60870 Edition 1
(Type 1, 3, 9, 11, 21, 126).