7 Operation
Maschinenfabrik Reinhausen GmbH 2019
324
5163667/06 EN
ETOS
®
IM
7.31.1.3.14 Analog multiplication
Description
MUL, analog multiplication
Inputs
Value (REAL32)
Multiplier (REAL32)
Outputs
Result (REAL32)
Overflow (BOOL)
Parameter
Constant multiplier (REAL32), -1,000,000...+1,000,000;
default = 1
Function
Result = Value * Multiplier * Constant multiplier
If the REAL32 range of numbers is exceeded, the
Overflow output becomes TRUE.
Initial state
All inputs and outputs are zero or FALSE.
Table 108: Analog multiplication function module
7.31.1.3.15 Analog division
Description
DIV, analog division
Inputs
Divident (REAL32)
Divisor (REAL32)
Outputs
Result (REAL32)
DivByZero (BOOL)
Overflow (BOOL)
Parameter
Constant divisor (REAL32), -1,000,000...+1,000,000;
default = 1
Function
Result = Dividend / Divisor / Constant Divisor
If dividing by zero, the DivByZero output becomes
TRUE and Result is set to zero.
If the REAL32 range of numbers is exceeded, the
Overflow output becomes TRUE and Result is set to
zero.
Initial state
All inputs and outputs are zero or FALSE.
Table 109: Analog division function module
7.31.1.3.16 Analog addition
Description
ADD, analog addition
Inputs
Input 1 (REAL32)
Input 2 (REAL32)
Outputs
Result (REAL32)
Overflow (BOOL)
Parameter
Offset (REAL32), -1,000,000...+1,000,000; default = 0