7 Operation
Maschinenfabrik Reinhausen GmbH 2019
190
5163667/06 EN
ETOS
®
IM
Insulating paper (only with IEC 60076-7 calculation method)
You can use this parameter to set whether the transformer is equipped with
thermally stabilized insulation paper or not. This parameter is used to calcu-
late the relative aging rate and is only relevant if you calculate the hot-spot
temperature in accordance with IEC 60076-7.
Transformer age
You can use this parameter to set the current age of the transformer in
years. This parameter is used to calculate the aging rate.
Anticipated service life
You can use this parameter to set the anticipated service life of the trans-
former in years. This parameter is used to calculate the aging rate.
To set the parameters for calculating the aging rate, proceed as follows:
1. Go to
Settings > Parameters > Rel. aging rate
.
2. Select the parameter you want.
3. Set the parameter you want.
4. Press the Accept button to save the modified parameter.
7.12.4 Displaying protective device status (optional)
The overview display shows you the current status of the connected protec-
tive devices.
Figure 141: Overview display of the status of the protective devices
To call up the overview display of the status of the protective devices, pro-
ceed as follows:
► Go to
Information > Protective devices
.