No.
Name
Description
Remedy
Q
1
1156
Operator maintenance
(OLTC) is required
Operator maintenance (OLTC) is
required.
Carry out operator maintenance
(OLTC).
-
1157
Plan operator maintenance
(transformer)
Operator maintenance (trans-
former) is required soon.
Carry out operator maintenance
(transformer) soon.
-
1158
Operator maintenance (trans-
former) is required
Operator maintenance (trans-
former) is required.
Carry out operator maintenance
(transformer).
-
1159
Cooling stage 1 error mes-
sage
There is a signal at the error input
for cooling stage 1
Check the connected cooling de-
vice for errors.
-
1160
Cooling stage 2 error mes-
sage
There is a signal at the error input
for cooling stage 2
Check the connected cooling de-
vice for errors.
-
1161
Cooling stage 3 error mes-
sage
There is a signal at the error input
for cooling stage 3
Check the connected cooling de-
vice for errors.
-
1162
Cooling stage 4 error mes-
sage
There is a signal at the error input
for cooling stage 4
Check the connected cooling de-
vice for errors.
-
1163
Cooling stage 5 error mes-
sage
There is a signal at the error input
for cooling stage 5
Check the connected cooling de-
vice for errors.
-
1164
Cooling stage 6 error mes-
sage
There is a signal at the error input
for cooling stage 6
Check the connected cooling de-
vice for errors.
-
1165
Plan oil filter replacement
The oil filter must be replaced
soon.
Replace the oil filter soon.
-
1166
Oil filter replacement is re-
quired
The oil filter must be replaced.
Replace the oil filter.
-
1167
Plan replacement or change
of contacts
The contacts must be replaced or
changed soon.
Replace or change the contacts
soon.
-
1168
Replacement or change of
contacts is required
The contacts must be replaced or
changed.
Replace or change the contacts.
-
1169
Contact wear calculation
The contact wear cannot be cal-
culated.
Check the settings, measurement
transformers, and device wiring.
-
1170
Plan oil change and cleaning
The oil must be changed and
cleaning must be carried out
soon.
Change the oil and clean soon.
-
1171
Oil change and cleaning re-
quired
The oil must be changed and
cleaning must be carried out.
Change the oil and clean.
-
1172
Desired power factor invalid
The set desired power factor is in-
valid.
Change the setting of the desired
power factor.
-
1173
Raise tap position
The device has issued a signal to
raise the tap position.
-
-
1174
Lower tap position
The device has issued a signal to
lower the tap position.
-
-
1175
Auto mode active
The device is in auto mode
-
-
1176
Remote mode active
The device is in remote mode
-
-
1177
BCD desired value invalid
BCD signal for desired value
specification is invalid or outside
the permitted range.
Check the signal source and
wiring of the BCD signal.
-