10 Uninstallation
Maschinenfabrik Reinhausen GmbH 2019
374
5163667/06 EN
ETOS
®
IM
10.2 Uninstalling the UI 1/UI 3 assembly
1. Remove the plug for the voltage measurement.
Figure 242: Voltage measurement
2.
WARNING!
Make sure that the current transformer is shorted. Other-
wise dangerously high voltages could occur. Remove the plug for the cur-
rent measurement.
Figure 243: Current measurement