7 Operation
Maschinenfabrik Reinhausen GmbH 2019
227
5163667/06 EN
ETOS
®
IM
Figure 171: Configuring data points
To configure a data point, proceed as follows:
1. Press the
+ new
button to add a new data point or press the
button to
edit a data point.
Figure 172: Adding a data point
2. Enter a
description
.
3. Select a
data type
and
register
.
4. Select the
byte order
of the sensor.
5. Only with IREG: Enter the
multiplier
.
6. Optional (only with IREG): Enter the
register
of the DISC for validation
and select the value for
validity
(High-active: 1 = valid; Low-active: 0 =
valid).
7. Optional (only with IREG): Enter the
minimum
and
maximum
value for
the validation. If the raw value is not within the set range, the value is in-
terpreted as being invalid.