You can set the following parameters:
▪ Calculation method
– IEC 60076-7
– IEEE Std C57.91
▪ Hot-spot factor (only with IEC 60076-7 calculation method)
▪ Gradient (only with IEC 60076-7 calculation method)
▪ Winding exponent (only with IEC 60076-7 calculation method)
▪ Oil time constant (only with IEC 60076-7 calculation method)
▪ k21 (only with IEC 60076-7 calculation method)
▪ k22 (only with IEC 60076-7 calculation method)
▪ Gradient (only with IEEE Std C57.91 calculation method)
▪ Exponent (only with IEEE Std C57.91 calculation method)
▪ Rated current of transformer (with IEC 60076-7 and IEEE Std C57.91 cal-
culation methods)
▪ Winding time constant (with IEC 60076-7 and IEEE Std C57.91 calcula-
tion methods)
Note the relevant standard for more information about the parameters.
To set the parameters for the hot-spot calculation, proceed as follows:
1. Go to
Settings > Parameters > Hot-spot
.
2. Select the parameter you want.
3. Set the parameter you want.
4. Press the
Accept
button to save the modified parameter.