7 Operation
Maschinenfabrik Reinhausen GmbH 2019
323
5163667/06 EN
ETOS
®
IM
Function
On Limit ≥ Off Limit setting:
▪ If the value of Input is greater than On Limit, Output
becomes TRUE.
▪ If the value of Input is less than or equal to Off Limit,
Output becomes FALSE.
On Limit < Off Limit setting:
▪ If the value of Input is greater than On Limit and at
the same time less than Off Limit, Output becomes
TRUE. Otherwise, the Output is FALSE.
Initial state
All inputs and outputs are zero or FALSE.
Table 107: Analog threshold value switch with hysteresis function module
On
Off
Input
Output
FALSE
TRUE
FALSE
Figure 229: Analog threshold value switch with the On Limit > Off Limit setting
Off
On
Input
Output
FALSE
TRUE
FALSE
FALSE
TRUE
TRUE
Figure 230: Analog threshold value switch with the On Limit < Off Limit setting