9 Messages
Maschinenfabrik Reinhausen GmbH 2019
351
5163667/06 EN
ETOS
®
IM
No.
Name
Description
Remedy
Q
1
1051
TDCG >> limit value
TDCG proportion is greater than
>> limit value.
Check the current operating con-
ditions of the transformer, sensor,
analog signal configuration and
the set limit value.
-
1052
Gen. temperature 1 > limit
value
Generic temperature 1 is greater
than > limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1053
Gen. temperature 1 >> limit
value
Generic temperature 1 is greater
than >> limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1054
Gen. temperature 1 < limit
value
Generic temperature 1 is less
than < limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1055
Gen. temperature 1 << limit
value
Generic temperature 1 is less
than << limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1056
Gen. temperature 2 > limit
value
Generic temperature 2 is greater
than > limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1057
Gen. temperature 2 >> limit
value
Generic temperature 2 is greater
than >> limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1058
Gen. temperature 2 < limit
value
Generic temperature 2 is less
than < limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1059
Gen. temperature 2 << limit
value
Generic temperature 2 is less
than << limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1060
Gen. temperature 3 > limit
value
Generic temperature 3 is greater
than > limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1061
Gen. temperature 3 >> limit
value
Generic temperature 3 is greater
than >> limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1062
Gen. temperature 3 < limit
value
Generic temperature 3 is less
than < limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-