9 Messages
Maschinenfabrik Reinhausen GmbH 2019
349
5163667/06 EN
ETOS
®
IM
No.
Name
Description
Remedy
Q
1
1027
Ambient temperature >> limit
value
Ambient temperature is greater
than >> limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1028
Ambient temperature < limit
value
Ambient temperature is less than
the < limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1029
Ambient temperature << limit
value
Ambient temperature is less than
the << limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1030
Bottom-oil temperature > limit
value
Bottom-oil temperature is greater
than > limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1031
Bottom-oil temperature >>
limit value
Bottom-oil temperature is greater
than >> limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1032
Bottom-oil temperature < limit
value
Bottom-oil temperature is less
than < limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1033
Bottom-oil temperature <<
limit value
Bottom-oil temperature is less
than << limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1034
Bubbling temperature > limit
value
Bubbling temperature is greater
than > limit value
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1035
Bubbling temperature >> limit
value
Bubbling temperature is greater
than >> limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1036
Bubbling temperature < limit
value
Bubbling temperature is less than
< limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1037
Bubbling temperature << limit
value
Bubbling temperature is less than
<< limit value.
Check the current operating con-
ditions of the transformer, temper-
ature sensor, analog signal con-
figuration, and the set limit value.
-
1038
C2H2 > limit value
C2H2 proportion is greater than >
limit value.
Check the current operating con-
ditions of the transformer, sensor,
analog signal configuration and
the set limit value.
-