21
Conduit
(50mm
(1.97 in.)
or less)
Main base unit
Extension base unit
80mm (3.15 in.) or more
*2
*1
*3
Serial installation
Represents the ceiling of panel,
wiring conduit, or component.
80mm (3.15 in.) or more
*1: These dimensions vary depending on the length of the
extension cable as follows:
AC06B cable.................... 450mm (17.71 in.) or less
AC12B cable.................... 1050mm (41.34 in.) or less
AC30B cable.................... 2850mm (112.20 in.) or less
*2: When a link module is
not used........................... 50mm (1.97 in.) or more
When using
φ
4.5mm
optical fiber cable,
or coaxial cable................ 100mm (3.94 in.) or more
When using
φ
8.5mm
optical fiber cable............. 130mm (5.12 in.) or more
*3: When a link module is
not used........................... 50mm (1.97 in.) or more
When using
φ
4.5mm
optical fiber cable,
or coaxial cable................ 100mm (3.94 in.) or more
When using
φ
8.5mm
optical fiber cable............. 130mm (5.12 in.) or more
(4) Unit mounting orientation
(a) Since the PLC generates heat, mount it in a well-ventilated location
and in the orientation shown below.
(b) Do not mount it in either of the orientations shown below.
Vertical position
Horizontal position
(5) Mount base unit on a flat surface.
If the mounting surface is uneven, this may strain the printed circuit boards
and cause malfunctions.