132
2100
In PLC parameter I/O allocation
settings, a special function module was
allocated to a location reserved for an I/
O module. Or, the opposite has
happened.
Reset the PLC parameter I/O allocation
setting to conform with the actual status
of the special function modules.
QnA
2101
13 or more A-series special function
modules (except for the A1SI61) that
can initiate an interrupt to the CPU
module have been installed.
Reduce the A series special function
modules (except the A1SI61) that can
make an interrupt start to the CPU
module to 12 or less.
Qn(H)
13 or more special function modules
(not counting the A(1S)I61) capable of
sending an interrupt to the CPU module
have been installed.
Keep the number of special function
modules that can initiate an interrupt
(with the exception of the A(1S)I61
module) to 12 or fewer.
QnA
2102
Seven or more A1SD51S have been
installed.
Keep the number of A1SD51S to six or
fewer.
Qn(H)
Seven or more serial communication
modules (excludes A (1S) J71QC24)
have been installed.
Keep the number of serial
communication modules (excludes
A(1S)J71QU24) installed to six or fewer.
QnA
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*3
The function version is B or later.
*4
The function version is A.
*5
The module whose first 5 digits of serial No. is 04101 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.