202
4122
• The dedicated instruction was
executed to the module mounted on
the extension base unit in the
redundant system.
• The instruction for accessing the
intelligent function module mounted
on the extension base unit from the
standby system at separate mode
was executed.
• Delete the dedicated instruction for
the module mounted on the extension
base unit.
• Delete the instruction for accessing
the intelligent function module
mounted on the extension base unit
from the standby system.
QnPRH
*6
4130
Instructions to read SFC step comment
(S(P).SFCSCOMR) and SFC transition
condition comment (S(P).SFCTCOMR)
are executed for the comment file in
ATA card
Target comment file is to be other than
the comment file in ATA card.
Qn(H)
*4
QnPH
*5
QnPRH
4131
The SFC program is started up by the
instruction while the other SFC program
has not yet been completed.
Check the SFC program specified by
the instruction. Or, check the executing
status of the SFC program.
QnU
4140
Operation where the input data is
special value ("-0", unnormalized
number, nonnumeric,
) is
performed.
Read the common information of the
error using the peripheral device, check
the error step corresponding to the
numerical value (program error part),
and correct it.
QnU
4141
Overflow occurs at operation.
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*3
The module whose first 5 digits of serial No. is 04012 or later.
*4
The module whose first 5 digits of serial No. is 07012 or later.
*5
The module whose first 5 digits of serial No. is 07032 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.
Содержание 13J851
Страница 2: ......
Страница 95: ...82 MEMO...
Страница 101: ...88 MEMO...
Страница 268: ...255 MEMO...