142
2112
• The module other than special
function module is specified by the
special function module dedicated
instruction.
Or, it is not the corresponding special
function module.
• The module model specified by the
special function module dedicated
instruction and that specified by the
parameter I/O assignment is different.
• Read the individual information of the
error using a peripheral device, and
check the special function module
dedicated instruction (network
instruction) that corresponds to the
value (program error part) to make
modification.
• Set the module model by PLC
parameter I/O assignment according
to the special function module
dedicated instruction setting.
Example) Although AJ71QC24N is
used actually, AJ71QC24 is set.
QnA
• The module other than intelligent
function module/special function
module is specified by the intelligent
function module/special function
module dedicated instruction.
Or, it is not the corresponding
intelligent function module/special
function module.
• There is no network No. specified by
the network dedicated instruction.
Or the relay target network does not
exit.
Read the individual information of the
error using a peripheral device, and
check the special function module /
special function module dedicated
instruction (network instruction) that
corresponds to the value (program error
part) to make modification.
QCPU
Rem
2113
The module other than network module
is specified bythe network dedicated
instruction.
QnA
Qn(H)
QnPH
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*3
The function version is B or later.
*4
The function version is A.
*5
The module whose first 5 digits of serial No. is 04101 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.