134
2103
• Two or more QI60/A1SI61 modules
are mounted in a single CPU system.
• Two or more QI60/A1SI61 modules
are set to the same control CPU in a
multiple CPU system.
• Two or more A1SI61 modules are
loaded in a multiple CPU system.
• Reduce the number of QI60/A1SI61
modules mounted in the single CPU
system to one.
• Change the number of QI60/A1SI61
modules set to the same control CPU
to only one in the multiple CPU
system.
• Reduce the number of A1SI61
modules to only one in the multiple
CPU system. When using an interrupt
module with each QCPU in a multiple
CPU system, replace it with the QI60.
(Use one A1SI61 max.
three QI60 modules or only the QI60
modules.)
Qn(H)
*3
QnPH
Two or more QI60, A1SI61 interrupt
modules have been mounted.
Install only 1 QI60, A(1S)I61 module.
Qn(H)
QnPRH
The QI60 is mounted.
Remove the QI60.
Rem
Two or more A1SI61 interrupt modules
have been mounted.
Install only 1 AI61 module.
QnA
Two or more QI60 modules are
mounted.
Reduce the QI61 modules to one.
Q00J/Q00/
Q01
*5
Two or more QI60 modules where
interrupt pointer setting has not been
made are mounted.
• Reduce the QI60 modules to one.
• Make interrupt pointer setting to the
second QI60 module and later.
Q00J/Q00/
Q01
*3
QnU
2104
At the MELSECNET/MINI auto refresh
network parameter settings, the module
allocation that was set is different from
the actual module models at the station
numbers in the link system.
Reset the network parameter
MELSECNET/MINI auto refresh unit
module allocation setting so that it
conforms to the station number of the
module that is actually linked.
QnA
2105
There are too many special function
modules that can use dedicated
instructions allocated (number of
modules installed).
(The total of the figures indicated below
is above 1344.)
*: When the expansion mode is used.
Reduce the number of special function
modules installed.
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
total 1344
(AD59
(AD57(S1)/AD58
(AJ71C24(S3/S6/S8)
(AJ71UC24
(AJ71C21(S1)
(AJ71PT32-S3/AJ71T32-S3
(AJ71QC24(R2,R4)
(AJ71ID1(2)-R4
+(AD75
modules installed 5)
modules installed 8)
modules installed 10)
modules installed 10)
modules installed 29)
modules installed 125)
modules installed 29)
modules installed 8)
modules installed 12)
*3
The function version is B or later.
*4
The function version is A.
*5
The module whose first 5 digits of serial No. is 04101 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.