102
1160
The program memory in the CPU
module is overwritten.
• Take noise reduction measures.
• Format the program memory, write all
files to the PLC, then reset the CPU
module, and RUN it again.
If the same error is displayed again,
the CPU module has hardware
failure. Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.
QnU
1161
The data of the device memory built in
the CPU module is overwritten.
• Take noise reduction measures.
If the same error is displayed again,
the CPU module has hardware
failure. Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.
1162
The error of the data held by the battery
in the CPU module is detected. (It
occurs when the automatic format is not
set.)
• Take noise reduction measures.
• Change the CPU main body or SRAM
card battery.
If the same error is displayed again,
the CPU module has hardware
failure. Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*4
Function version is B or later.
*5
Function version is A.
*6
The module whose first 5 digits of serial No. is 04101 or later.
*7
The module whose first 5 digits of serial No. is 07032 or later.
*8
The module whose first 5 digits of serial No. is 08032 or later.
*9
The module whose first 5 digits of serial No. is 09012 or later.
*10 The Universal model QCPU except the Q02UCPU.
Содержание 13J851
Страница 2: ......
Страница 95: ...82 MEMO...
Страница 101: ...88 MEMO...
Страница 268: ...255 MEMO...
Страница 269: ......