234
6111
The control system does not have
enough file register capacity for the file
registers specified in the tracking
settings.
(This can be detected from the control
system or standby system of the
redundant system.)
Switch to the file registers of which
capacity is greater than the file registers
specified in the tracking settings.
QnPRH
6112
File registers greater than those of the
standby system were tracked and
transmitted from the control system.
(This can be detected from the standby
system of the redundant system.)
Switch to the file registers of which
capacity is greater than the file registers
specified in the tracking settings.
6120
• A start was made without the tracking
cable being connected.
• A start was made with the tracking
cable faulty.
• As the tracking hardware on the CPU
module side was faulty,
communication with the other system
could not be made via the tracking
cable.
(This can be detected from the control
system or standby system of the
redundant system.)
Make a start after connecting the
tracking cable. If the same error still
occurs, this indicates the tracking cable
or CPU module side tracking
transmission hardware is faulty.
(Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.)
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*1
The module whose first 5 digits of serial No. is 09012 or later.