174
3042
The system file that have stored the
remote password setting information is
damaged.
• With GX Developer, write [PLC
parameter/netwark parameter/remote
password] to a valid drive then reload
the power supply for system and/or
reset the CPU module. If the same
error occurs, it is thought to be a
hardware error. (Contact your local
Mitsubishi representative.)
• When a valid drive for parameter is
set to other than [program memory],
set the parameter file (PARAM) at the
boot file setting to be able to transmit
to the program memory.
With GX Developer, write [PLC
parameter/netwark parameter/remote
password] to a valid drive then reload
the power supply for system and/or
reset the CPU module. If the same
error occurs, it is thought to be
hardware error. (Contact your local
Mitsubishi representative.)
Qn(H)
*4
QnPH
*4
QnPRH
*4
3100
In a multiple CPU system, the
MELSECNET/G module controlled by
another CPU is specified as the head I/
O number of the MELSECNET/G
module.
• Delete the net work parameter of the
MELSECNET/G module controlled by
another CPU.
• Change the setting to the head I/O
number of the MELSECNET/G
module controlled by host CPU.
Qn(H)
*6
QnU
The network parameter of the
MELSECNET/G operating as the
normal station is overwritten to the
control station.
Or, the network parameter of the
MELSECNET/G operating as the
control station is overwritten to the
normal station.
(The network parameter is updated on
the module by resetting.)
Reset the CPU module.
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*3
The module whose first 5 digits of serial No. is 04012 or later.
*4
The module whose first 5 digits of serial No. is 07032 or later.
*5
The MELSECNET/H module whose first 5 digits of serial No. is 08102 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.