128
2012
The GOT is bus-connected to the main
base unit of the redundant system.
The following errors are detected in the
CPU redundant system compatible with
the extension base unit.
• The base unit other than the
Q6 WRB is connected to the
extension stage No.1.
• The base unit is connected to any
one of the extension stages No.2 to
No.7, although the Q6 WRB does
not exist in the extension stage No.1 .
• The other system CPU module is
incompatible with the extension base
unit.
• The Q5 B, QA1S6 B, or QA6 B is
connected.
• The number of slots of the main base
unit for both systems is different.
Information of the Q6 WRB cannot
be read correctly.
• Remove a bus connection cable for
GOT connection connected to the
main base unit.
• Use the Q6 WRB (fixed to the
extension stage No.1)
• Use the CPU module compatible with
the extension base unit for the other
system.
• Do not use the Q5 B, QA1S6 B, or
QA6 B for the base unit.
• Use the main base unit which has the
same number of slots.
• Hardware failure of the Q6 WRB.
(Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.)
QnPRH
*6
2013
Stage number of the Q6 WRB is
recognized as other than extension
stage No.1 in the redundant system.
Hardware failure of the Q6 WRB.
(Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.)
2020
The following errors are detected in the
redundant system.
• At power-on/reset, the standby
system has detected the error in the
path between the control system and
the Q6 WRB.
• The standby system has detected the
error in the path between the host
system CPU and the Q6 WRB at
END processing.
Check to see if the extension cable
between the main base unit and the
Q6 WRB is connected correctly. If not,
connect it after turning OFF the main
base unit where the extension cable will
be connected.
If the cable is connected correctly,
hardware of the CPU module,
Q6 WRB, or extension cable is faulty.
(Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.)
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*3
The function version is B or later.
*4
The function version is A.
*5
The module whose first 5 digits of serial No. is 04101 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.