116
1418
In the redundant system, at power-on/
reset or switching system, the control
system cannot access the extension
base unit since it failed to acquire the
access right.
Reset the CPU module and RUN it
again. If the same error is displayed
again, the CPU module, the Q6 WRB,
or hardware of extension cable is faulty.
(Contact your local Mitsubishi
representative, explaining a detailed
description of the problem.)
QnPRH
*9
1421
Hardware fault at the system
management module AS92R.
This suggests a system management
module AS92R hardware fault.
(Contact your local Mitsubishi
representative.)
Q4AR
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*4
Function version is B or later.
*5
Function version is A.
*6
The module whose first 5 digits of serial No. is 04101 or later.
*7
The module whose first 5 digits of serial No. is 07032 or later.
*8
The module whose first 5 digits of serial No. is 08032 or later.
*9
The module whose first 5 digits of serial No. is 09012 or later.
*10 The Universal model QCPU except the Q02UCPU.