10
(5) AD75P -S3 module
(a) When wiring using a cable of 2 m (6.56 ft.) or less
Wire the cables for external wiring between a drive unit and an
external device using the shortest possible distance.
Install the drive unit on the same panel.
A68RB
A
D
7
5
Drive
unit
Connector for external wiring
Cable for external wiring (2 m (6.56 ft.) or less)
Cable clamp
P
o
w
e
r
su
p
p
ly
m
od
u
le
P
o
w
e
r
su
p
p
ly
m
od
u
le
(b) When wiring using a cable between 2 m (6.56 ft.) and 10 m (32.81 ft.)
Install a ferrite core.
Wire the cables for external wiring between a drive unit and
external device using the shortest possible distance.
A68RB
Connector for external wiring
Ferrite core (TDK's ZCAT3035-1330)
Cable for external wiring
(between 2 m (6.56 ft.) and 10 m (32.81 ft.))
Cable clamp
A
D
7
5
P
o
w
er
s
up
p
ly
m
od
u
le
P
o
w
er
s
up
p
ly
m
od
u
le
Drive
unit
(c) Ferrite core and cable clamp types and required quantities
• Cable clamp
Type: AD75CK (Mitsubishi Electric)
• Ferrite core
Type: ZCAT3035-1330 (TDK ferrite core)
• Required quantity
Required Qty
Cable length
Prepared part
1 axis
2 axis
3 axis
Within 2m (6.6ft.)
AD75CK
1
1
1
AD75CK 1 1 1
2m (6.6ft.) to 10m (32.8ft.)
ZCAT3035-1330
1 2 3
(d) Cable clamp mounting position
AD
75
20 30cm
Inside control panel
AD75CK
(7.87 11.81inch)