228
6100
A CPU module tracking memory error
was detected during initial.
(This can be detected from the control
system or standby system of the
redundant system.)
Hardware fault of the CPU module.
(Please contact your local nearest
Mitsubishi or sales representative,
explaining a detailed description of the
problem. Change the CPU modules in
order of the standby system CPU
module and control system CPU
module.)
Q4AR
• An error (e.g. retry limit exceeded)
occurred in tracking data
transmission.
(This error may be caused by
tracking cable removal or other
system power-off (including reset).)
• The error occurred at a startup since
the redundant system startup
procedure was not followed.
• Check the CPU module or tracking
cable. If the error still occurs, this
indicates the CPU module or tracking
cable is faulty. (Contact your local
Mitsubishi representative, explaining
a detailed description of the problem.)
• Confirm the redundant system startup
procedure, and execute a startup
again.
QnPRH
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*1
The module whose first 5 digits of serial No. is 09012 or later.