(6) CC-Link module
(a) Make sure to ground the twisted pair cables (FANC-CB, 0.5 mm
2
(0.00077inch
2
) 3) connected to the master station, local station and
all modules in remote stations.
As this cable is shielded type, strip a part of the outer insulation layer
to expose the shield as shown below, and make the shield contact with
the control panel in the largest area as possible.
CC-Link cable
Shield
Control panel
PLC
CC-Link master station
Remote
station
Remote
station
Local
station
Control panel
Perform grounding in the areas
indicated by
Always use the specified cable
for the cables indicated by
Also, position the grounding point closer to the outlet of control panel
and within 30cm (11.81 inch) from module terminals.
(b) Always use the specified CC-Link dedicated cable.
(c) Connect the CC-Link module and each CC-Link station to the FG line
inside the control panel with both the FG and SLD terminals as shown
below.
Terminal
resistor
Master module
Remote module
Local module
Terminal
resistor
CC-Link
dedicated
cable
CC-Link
dedicated
cable
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
(Blue)
(White)
(Yellow)
[Simplified diagram]