The battery is dead.
The program memory in the CPU
module is faulty.
• Check the battery to see if it is dead
or not. If dead, replace the battery.
• Take noise reduction measures.
• Format the program memory, write all
files to the PLC, then reset the CPU
module, and RUN it again.
If the same error is displayed again,
the possible cause is a CPU module
hardware fault. (Contact your local
Mitsubishi representative, explaining
a detailed description of the problem.)
Qn(H)
QnPH
*7
QnPRH
1107
The work area RAM in the CPU module
is faulty.
This suggests a CPU module hardware
fault. (Contact your local Mitsubishi
representative.)
QnPRH
1108
1109
Qn(H)
*8
QnPH
*8
QnPRH
*9
1110
A fault was detected by the initial check
of the tracking hardware.
QnPRH
1111
A tracking hardware fault was detected.
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*4
Function version is B or later.
*5
Function version is A.
*6
The module whose first 5 digits of serial No. is 04101 or later.
*7
The module whose first 5 digits of serial No. is 07032 or later.
*8
The module whose first 5 digits of serial No. is 08032 or later.
*9
The module whose first 5 digits of serial No. is 09012 or later.
*10 The Universal model QCPU except the Q02UCPU.