210
4400
No SFCP or SFCPEND instruction in
SFC program.
Write the program to the CPU module
again using GX Developer.
QnA
Qn(H)
QnPH
QnPRH
4410
The block number designated by the
SFC program exceeds the range.
QnA
Q00J/Q00/
Q01
*2
Qn(H)
QnPH
QnPRH
QnU
4411
Block number designations overlap in
SFC program.
4420
A step number designated in an SFC
program exceeds the range.
4421
Total number of steps in all SFC
programs exceed the maximum.
QnA
Q00J/Q00/
Q01
*2
Qn(H)
QnPH
QnPRH
QnU
4422
Step number designations overlap in
SFC program.
4423
The total number of (maximum step
No.+1) of each block exceeds the total
number of step relays.
Correct the total number of step relays
so that it does not exceed the total
number of (maximum step No.+1) of
each block.
Q00J/Q00/
Q01
*2
QnU
4430
The SFC program cannot be executed.
• The data of the block data setting is
illegal.
• The SFC data device of the block
data setting is beyond the device
setting range set in the PLC
parameter.
• Write the program to the CPU module
again using GX Developer.
• After correcting the setting of the SFC
data device, write it to the CPU
module.
• After correcting the device setting
range set in the PLC parameter, write
it to the CPU module.
4431
The SFC program cannot be executed.
• The block parameter setting is
abnormal.
Write the program to the CPU module
again using GX Developer.
4432
The SFC program cannot be executed.
• The structure of the SFC program is
illegal.
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*3
The module whose first 5 digits of serial No. is 04012 or later.
*4
The module whose first 5 digits of serial No. is 07012 or later.
*5
The module whose first 5 digits of serial No. is 07032 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.