108
1310
An interruption has occurred although
there is no interrupt module.
Any of the mounted modules is
experiencing a hardware fault.
Therefore, check the mounted modules
and change the faulty module. (Contact
your local Mitsubishi representative.)
1311
An interrupt request from other than the
interrupt module was detected.
Take action so that an interrupt will not
be issued from other than the interrupt
module.
Q00J/Q00/
Q01
*4
QnU
An interrupt request from the module
where interrupt pointer setting has not
been made in the PLC parameter dialog
box was detected.
• Correct the interrupt pointer setting in
the PLC system setting of the PLC
parameter dialog box.
• Take measures so that an interrupt is
not issued from the module where the
interrupt pointer setting in the PLC
system setting of the PLC parameter
dialog box has not been made.
Correct the interrupt setting of the
network parameter. Correct the
interrupt setting of the intelligent
function module buffer memory.
Correct the basic program of the
QD51.
Q00J/Q00/
Q01
*5
QnPRH
QnU
1401
• There was no response from the
intelligent function module/special
function module in the initial
processing.
• The size of the buffer memory of the
intelligent function module/special
function module is invalid.
• The unsupported module is mounted.
When the unsupported module is
mounted, remove it.
When the corresponding module is
supported, this suggests the intelligent
function module/special function
module, CPU module and/or base unit
is expecting a hardware fault (Contact
your local Mitsubishi representative.)
QCPU
Rem
When PLC parameter I/O allocation
was being made, there was no return
signal from the special function module
during initial processing stage.(When
error is generated, the head I/O number
of the special function module that
corresponds to the common information
is stored.)
The CPU module, base unit and/or the
special function module that was
accessed is experiencing a hardware
fault. (Contact your local Mitsubishi
representative.)
QnA
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*4
Function version is B or later.
*5
Function version is A.
*6
The module whose first 5 digits of serial No. is 04101 or later.
*7
The module whose first 5 digits of serial No. is 07032 or later.
*8
The module whose first 5 digits of serial No. is 08032 or later.
*9
The module whose first 5 digits of serial No. is 09012 or later.
*10 The Universal model QCPU except the Q02UCPU.