48
POINT
(1) Use the thickest possible (max. 2 mm
2
(14 AWG)) wires for the 100/200
VAC and 24 VDC power cables. Be sure to twist these wires starting at
the connection terminals. For wiring a terminal block, be sure to use a
solderless terminal. To prevent short-circuit due to loosening screws,
use the solderless terminals with insulation sleeves of 0.8 mm (0.03
inch) or less thick. The number of the solderless terminals to be
connected for one terminal block are limited to 2
Terminal block
Solderless terminals
with insulation sleeves
(2) When connection is made between the LG and FG terminals, be sure to
ground the wire.
When it is not grounded with LG and FG terminals connected, it will be
susceptible to noise.
Note that each LG terminal has half the potential of the input voltage;
you might get an electric shock if you touch it.