188
3106
The CC-Link link refresh range
exceeded the file register capacity.
Change the file register file for the one
refresh-enabled in the whole range.
Qn(H)
*1
QnPH
QnPRH
QnU
The network refresh parameter for
CC-Link is out of range.
Check the parameter setting.
QCPU
Rem
3107
• The CC-Link parameter setting is
incorrect.
• The set mode is not allowed for the
version of the mounted CC-Link
module.
Check the parameter setting.
Rem
3200
The parameter setting is illegal.
• Though Block 0 was set to "Automatic
start" in the SFC setting of the PLC
parameter dialog box, Block 0 does
not exist.
Read the common information of the
error using the peripheral device, check
error step corresponding to its
numerical value (program error
location), and correct the problem.
QnA
Q00J/Q00/
Q01
*1
QnPH
QnPRH
QnU
3201
The block parameter setting is illegal.
QnA
Qn(H)
QnPH
QnPRH
3202
The number of step relays specified in
the device setting of the PLC parameter
dialog box is less than that used in the
program.
3203
The execution type of the SFC program
specified in the program setting of the
PLC parameter dialog box is other than
scan execution.
QnA
Qn(H)
QnPH
QnPRH
QnU
3300
The start I/O number in the intelligent
function module parameter set on
GX Configurator differs from the actual
I/O number.
Check the parameter setting.
QCPU
Rem
3301
The refresh setting of the intelligent
function module exceeded the file
register capacity.
Change the file register file for the one
which allows refresh in the whole range.
Q00J/Q00/Q01
Qn(H)
*1
QnPH
QnPRH
QnU
The intelligent function module's refresh
parameter setting is outside the
available range.
Check the parameter setting.
QCPU
Rem
3302
The intelligent function module's refresh
parameter are abnormal.
Check the parameter setting.
QCPU
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*3
The module whose first 5 digits of serial No. is 04012 or later.
*4
The module whose first 5 digits of serial No. is 07032 or later.
*5
The MELSECNET/H module whose first 5 digits of serial No. is 08102 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.
Содержание 13J851