182
3102
A MELSECNET/G network parameter
error was detected.
• Correct and write the network
parameters.
• If the error occurs after correction, it
suggests a hardware fault. (Contact
your local Mitsubishi representative.)
Qn(H)
*6
QnU
• The network module detected a
network parameter error.
• A MELSECNET/H network parameter
error was detected.
The station No. specified in pairing
setting are not correct.
• The stations are not numbered
consecutively.
• Pairing setting has not been made for
the CPU module at the normal
station.
Refer to the troubleshooting of the
network module, and if the error is due
to incorrect pairing setting, reexamine
the pairing setting of the network
parameter.
QnPRH
The MELSECNET/G module whose
first 5 digits of serial No. is "09041" or
earlier is mounted.
Mount the MELSECNET/G module
whose first 5 digits of serial No. is
"09042" or later.
QnU
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*3
The module whose first 5 digits of serial No. is 04012 or later.
*4
The module whose first 5 digits of serial No. is 07032 or later.
*5
The MELSECNET/H module whose first 5 digits of serial No. is 08102 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.