126
2010
• More than applicable number of
extension base units have been used.
• When a GOT was bus-connected, the
CPU module was reset while the
power of the GOT was OFF.
• Use the allowable number of
extension base units or less.
• Power on the PLC and GOT again.
Q00J/Q00/
Q01
*3
QnPRH
Q02U
2011
The QA1S6 B or QA6 B was used as
the base unit.
Do not use the QA1S6 B or QA6 B
as the base unit.
Q00J/Q00/
Q01
*3
QnPRH
QnU
Error
Code
(SD0)
Error Contents and Cause
Corrective Action
Corresponding
CPU
*3
The function version is B or later.
*4
The function version is A.
*5
The module whose first 5 digits of serial No. is 04101 or later.
*6
The module whose first 5 digits of serial No. is 09012 or later.
*7
The Universal model QCPU except the Q02UCPU.