12
3.1.4 Power supply module
The precautions required for each power supply module are described below.
Always observe the items noted as precautions.
Model name
Precautions
A61P, A62P
N/A
A63P
Use a CE-compliant 24VDC power supply in the control panel.
A61PEU, A62PEU
Make sure to short and ground the LG and FG terminals.
3.1.5 Base unit
The following table shows models of base units that are compatible with EMC
instructions.
Type Model
name Applicability
A38HBEU Applicable
Main base unit
A3 B, A38HB
Not applicable
Extension base unit A5 B, A6 B Applicable
3.1.6 Ferrite core
Use of ferrite cores is effective in reducing the conduction noise in the band of
about 10 MHz and radiated noise in 30 to 100 MHz band.
It is recommended to attach ferrite cores when the shield of the shielded cable
coming out of control panel does not work effectively, or when emission of the
conduction noise from the power line has to be suppressed
1
The model of ferrite
core used in our tests is the TDK-made ZCAT3035.
Install the ferrite core immediately before pulling the cables out of the panel. If the
installation position is not appropriate, the effect of ferrite may be diminished.
1 To response with CE(EN61131-2/A12), make sure to mount 2 or more
ferrite cores onto the power supply line. The mounting position should be as
near the power supply module as possible. Use the ferrite core of
ZCAT2235-1030A.
Ferrite core
Type: ZCAT 2235-1030A(TDK ferrite core)